Description:
Station type surge arrester is designed and manufactured to protect electrical equipment in the power station. It is characterized by excellent non-linear properties, quick steep wave response, strong current-flow capacity, and anti-aging ability, etc. All these features enhance the level of protection and reliability. Furthermore, the arrester is designed to be easy for installation and maintenance.
Features:
1. Excellent protective performance.
2. Good resistance to pollution.
3. Easy installation and maintenance.
Techincal data:
|
Type
|
Rated voltage (kV)
|
MCOV (kV)
|
Max 0.5μs discharge woltage (kV)1
|
Max switching surge protective level At classifying current levels (kV)2
|
Max discharge voltage using an 8/20 current wave (kV)
|
|
1.5kA
|
3KA
|
5KA
|
10KA
|
20KA
|
40KA
|
|
HDA4-54
|
54
|
42
|
135
|
100
|
107
|
112
|
117
|
125
|
136
|
151
|
|
HDA4-60
|
60
|
48
|
150
|
111
|
119
|
125
|
130
|
139
|
151
|
168
|
|
HDA4-72
|
72
|
57
|
178
|
132
|
141
|
148
|
154
|
165
|
179
|
199
|
|
HDA4-90
|
90
|
70
|
225
|
166
|
178
|
187
|
195
|
208
|
226
|
251
|
|
HDA4-90
|
90
|
74
|
238
|
176
|
188
|
198
|
206
|
220
|
239
|
265
|
|
HDA4-96
|
96
|
76
|
238
|
176
|
188
|
198
|
206
|
220
|
239
|
265
|
|
HDA4-108
|
108
|
84
|
269
|
199
|
213
|
224
|
233
|
249
|
270
|
300
|
|
HDA4-108
|
108
|
88
|
275
|
203
|
218
|
228
|
238
|
254
|
276
|
306
|
|
HDA4-120
|
120
|
98
|
306
|
235
|
242
|
254
|
265
|
283
|
307
|
341
|
|
HDA4-132
|
132
|
106
|
332
|
254
|
263
|
276
|
287
|
307
|
333
|
370
|
|
HDA4-144
|
144
|
115
|
360
|
276
|
285
|
299
|
312
|
333
|
361
|
402
|
|
HDA4-168
|
168
|
131
|
416
|
319
|
330
|
346
|
360
|
385
|
418
|
464
|
|
HDA4-172
|
172
|
140
|
438
|
336
|
347
|
363
|
379
|
405
|
439
|
488
|
|
HDA4-180
|
180
|
144
|
450
|
345
|
357
|
374
|
390
|
416
|
452
|
502
|
|
HDA4-192
|
192
|
152
|
478
|
365
|
377
|
395
|
412
|
440
|
477
|
531
|
|
HDA4-228
|
228
|
180
|
568
|
436
|
450
|
472
|
492
|
526
|
570
|
634
|
|
HDA4-258
|
258
|
209
|
659
|
526
|
522
|
547
|
570
|
609
|
661
|
735
|
|