No.
|
Item
|
Unit
|
Value
|
1
|
Rated voltage
|
KV
|
12
|
2
|
Rated lighting impulse withstand voltage
|
KV
|
Inter phase or to ground 75,
fructure 80
|
3
|
Rated short-time power frequency withstand voltage
|
KV
|
Inter phase or to ground 42,
fructure 48
|
4
|
Rated short-circuit breaking current
|
KA
|
20,25
|
31.5
|
40
|
5
|
Rated current
|
A
|
630/1250/1600
/2000/2500/3150
|
6
|
Rated thermo stability current(valid)
|
KA
|
25
|
31.5
|
40
|
7
|
Rated dynamic stability current(peak)
|
KA
|
63
|
80
|
100
|
8
|
Rated short-circuit making current(peak)
|
KA
|
63
|
80
|
100
|
9
|
Rated operations of short-circuit breaking current
|
Times
|
50(40kA is 30)
|
10
|
Rated working current of over current and tripping coil
|
A
|
5
|
11
|
Rated operating sequence
|
|
0-0.3s-CO-180s -CO
|
12
|
Rated current of auxiliarate switch
|
A
|
AC10,DC5
|
13
|
Rated voltage of energy saving release
|
V
|
AC.DC220 AC.DC110
|
14
|
Closing time
|
Times
|
≤75
|
15
|
Opening time
|
|
≤60(40)
|
16
|
Power of energy saving motor
|
W
|
275
|
17
|
Energy saving time
|
S
|
≤15
|
18
|
Mechanical life
|
Times
|
20000
|